Beijing HiYi Technology Co., Ltd

Beijing HiYi Technology Co., Ltd

Manufacturer from China
Verified Supplier
5 Years
Home / Products / Addressable Fire Alarm Panel /

FP300 Addressable Fire Alarm Panel

Contact Now
Beijing HiYi Technology Co., Ltd
Visit Website
City:beijing
Province/State:beijing
Contact Person:Lisa Niu
Contact Now

FP300 Addressable Fire Alarm Panel

Ask Latest Price
Video Channel
Brand Name :HiYi
Model Number :FP300
Certification :CE
Place of Origin :China
MOQ :1 set
Price :USD 600 - 750 / set
Payment Terms :T/T, Western Union, MoneyGram, D/P, D/A, L/C
Supply Ability :1000 SET / week
Delivery Time :1-10 work days
Packaging Details :Carton size : 30X20X8 cm
Product name :Control Panel
Mains Supply :230VAC (-15%, +10%). 47 ~ 63Hz. Max current 0.8A
Mains Fuse :T3.15AL250V
Operating Voltage :18.5 ~ 30VDC
Recommended Mains Cable: Screened or standard/black mains cable, :Screened or standard/black mains cable
cable size :0.75mm2
Max. Charging Current :1.2A
Max. Battery Supply Current :4A (when the Mains is disconnected)
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

Intelligent LPCB Approved Addressable Fire Alarm System Control Panel

Addressable Fire Alarm System
FP300 Addressable Fire Alarm Control Panel

OVERVIEW

The purpose of the FP300 Fire Alarm Control Panel (FACP) is to monitor input signals, give indications and possibly activate outputs as programmed.
It is designed to comply with EN 54-2 with qualities of simple installation, operation and easy maintenance. The FP300 panel is an addressable fire detection panel with 1 loop of 324 addressable points and expansion capabilities. It is compatible with other peripherals made by our company with its own protocol.

FP300 Addressable Fire Alarm Panel

FEATURES & BENEFITS

  • Up to 324 addresses on one loop.
  • An easy to read, 4.3'' color screen LCD with a resolution of 480×272.
  • Zone indication and control panel(ZCP) for 32 zones gives a quick indication of the location of an alarm.
  • Record capacity of 1000 historical events for each of historical fire, historical fault and historical operation.
  • An independently programmable conventional sounder circuit output.
  • Integral power supply and battery.
  • Integral printer.
  • Flexible and intuitive cause and effect programming on front panel.
  • Zone test, point test and module start/stop testing facilitate the commissioning
  • U-disk interface makes the load and save of configuration or historical data convenient for system commissioning and maintenance.
  • Hierarchy management with three access levels.
  • Anti-tamper protection by a key lock.
  • CAN bus for interconnection of up to 20 FACPs and RS485 for connection with up to 30 fire indicating panels per FACP.

FP300 Addressable Fire Alarm Panel

APPLICATION

Fire alarm system is mostly used for laying fire system in office and commercial places. Any building needs fire alarm system, which can effectively prevent the occurrence of fire and give warning from the source.

PRODUCT PARAMENTERS

Mains supply 230VAC (-15%, +10%). 47 ~ 63Hz. Max current 0.8A
Mains fuse T3.15AL250V

Operating voltage

18.5 ~ 30V
Recommended mains cable Recommended mains cable
Screened or standard/black mains cable, cable size 0.75mm2
Power rating Imax.a=1.2A; Imax.b=2.6A; Imin=0.65A
Max. charging current 1.2A
Max. internal resistance of battery 1.5Ω
Battery fuse F8AL250V
Quiescent current (full loaded) < 0.4A